We blogged previously about the State/OIG Management Assistance Report sounding the alarm over the fire alarm system at the U.S. Embassy in Kabul (see U.S. Embassy Kabul: Fire Alarm System Needs Prompt Attention or #MustHaveNoFireBeforeMarch2019).
We received a reaction about the OIG report basically saying “hey, I agree with all the violations listed by the OIG”. Our correspondent also thought the “funniest thing” included in the report is that OBO challenged the OIG qualifications. There appears to be serious concerns that sound fire protection engineering judgements are being overridden “on a regular basis.” There are also some questions/allegations about the qualifications of OBO folks making decisions concerning fire protection engineering — that if true, could potentially have serious consequences.
OPM says that all Professional Engineering positions require a basic degree in engineering or a combination of education and experience — college-level education, training, and/or technical experience that furnished (1) a thorough knowledge of the physical and mathematical sciences underlying engineering, and (2) a good understanding, both theoretical and practical, of the engineering sciences and techniques and their applications to one of the branches of engineering. Also that the adequacy of such background must be demonstrated by one of the following: 1) Professional registration or licensure — Current registration as an Engineer Intern (EI), Engineer in Training (EIT)1, or licensure as a Professional Engineer (PE) by any State, the District of Columbia, Guam, or Puerto Rico. 2) Written Test — Evidence of having successfully passed the Fundamentals of Engineering (FE)2 examination or any other written test required for professional registration by an engineering licensure board in the various States, the District of Columbia, Guam, and Puerto Rico. Read more here.
In any case, you know that State/PA refused to respond to us during Tillerson’s watch but with Pompeo’s new guards in, we thought we should try asking questions again from its media professionals, coz, why not, hey?
We did receive a PA response months ago that says “we’ll look into it but may not have anything over the weekend”. Lordy, short weekends and long weekends have come and gone and we have not heard anything back via email, fax, sign language, or telephatic signal. Our follow-up email appeared to have also ended up in a black hole of bureaucratic shrugger-swagger.
In any case, we’ve addressed the same questions to State/OIG, and those folks reliably read and respond to email inquiries, and we received the following:
Ensuring the safety and security of Department personnel is paramount for the OIG. We give careful consideration to allegations relating to safety and security issues, including the one involving the Office of Fire Protection. Additionally, if anyone becomes aware of something that jeopardizes the safety and security of Department employees, they should report it immediately to the OIG hotline at OIG.state.gov/HOTLINE or at 1-800-409-9926.
About that report, here are a couple of examples that we understand, requires some folks to wear brown paper bags over their heads when reading:
OBO’s Technical Comment 10 | OBO disagreed with OIG’s statement: “According to PAE, a secondary loop was installed. However, rather than being routed separately, the existing fiber optic cables run in a parallel path. Because the fiber optic cables run in the same direction (as opposed to opposite directions representing a redundant circuit), damage to one part of the network can render sections of the network inoperable.” OBO stated that “it is perfectly acceptable for cables to run in the same direction. They cannot run in the same conduit. Additionally, the secondary loop is, in fact, a redundant circuit since there are two paths of travel one from the original loop and one from the secondary loop.”
OIG’s Reply | OIG agrees that cables can run in the same direction but cannot run in the same conduit. OIG found, however, that a number of the runs currently installed at Embassy Kabul did, in fact, have fiber optic cables bundled together in the same conduit. The photo below shows the current configuration at Embassy Kabul in which fiber optic cables are bundled together in the same conduit. This is contrary to NFPA standards for a redundant path. OIG made no changes to the report on the basis of this comment.
TA-DAA! Somebody stop these wild cables from running in the same conduit!
OBO’s Technical Comment 13 | OBO disagreed with OIG’s conclusion that “the improper installation of key components of Embassy Kabul’s fire alarm system needs immediate attention because of the potential safety risk to personnel and property.” OBO stated that it disagreed with OIG’s underlying assumptions and that OIG’s scope contained flaws.
OIG’s Reply | As set forth in this report, OBO is not in compliance with NFPA 72 regarding the requirement for a redundant path. In addition, a number of the runs currently installed at Embassy Kabul have fiber optic cables bundled together in the same conduit, which similarly fails to comply with NFPA 72. The NFPA codes and standards are designed to minimize the risk and effects of fire by establishing criteria for building, processing, design, service, and installation around the world. Failure to adhere to these requirements thus presents potential risk to embassy personnel and property. Therefore, the improper installation of key components of Embassy Kabul’s fire alarm system requires immediate attention. OIG made no changes to the report on the basis of this comment.
#